When cyber attacks change physical processes: lessons from the 2026 refrigeration attacks
In October and November 2026, attackers changed the settings on connected refrigeration controllers across Europe. In France, the government reports around 700 sites affected, extensive food losses and at least 15 fires. A second wave in early November reached at least ten more countries, and some UK meat processors were caught up in it.
Nobody stole any data. The attackers changed how equipment behaved, and the damage was physical: spoiled stock, fire and lost trading. For anyone responsible for a production site, that is the part worth understanding. The equipment was a refrigeration controller rather than a factory PLC, but the pattern of exposure, access and changed settings applies to any connected control system.
This guide sets out what is confirmed, what is not, why a setting change becomes a physical incident, and the controls that matter most. It draws on official advisories from France’s ANSSI and CERT-FR, the US CISA and FBI, the UK NCSC and NIST, with sources listed at the end. It reflects public information available in late November 2026, and counts or attributions may change as investigations continue.
In short
- What happened. Attackers got into refrigeration controllers over the internet and changed the defrost and temperature settings. France says an Iranian state-linked unit did the October attacks. Nobody has officially said who did the November ones.
- Why it matters to a factory. If a controller can be reached from the internet and still has a weak or factory password, someone else can change what it does. That risk is not new. These attacks show what it costs when it happens.
- What to do. Know what you have and every way into it. Take control equipment off the open internet. Control how suppliers connect. Protect the settings that matter. Record who changes what. Prove you can restore a program. No single product does all of that.
What happened
| Date | What happened | Status |
|---|---|---|
| 11 to 12 October | Refrigeration controllers at about 700 French retail sites compromised. Defrost settings altered, stock lost, at least 15 fires. | Official (French government) |
| 12 to 16 October | CERT-FR alert names Danfoss AK-SM and AK-SC, Copeland xweb and Dixell xweb controllers and advises removing internet exposure. | Official technical alert |
| 1 to 2 November | Second wave across at least ten more European countries, affecting over 100 retail locations. | Reported; counts provisional |
| 3 November | NCSC chief executive Richard Horne refers to “disruption of refrigeration units across Europe”. NCSC says a handful of UK organisations were alerted. | Official UK statement |
| 5 November | CISA, FBI and three other US agencies publish a joint fact sheet on hardening refrigeration and cold chain systems. | Official guidance |
| 9 November | France attributes the October campaign to Shahid Kaveh, a cyber unit linked to Iran’s Islamic Revolutionary Guard Corps. | Official attribution, October only |
| 13 November | Germany’s BSI warns that some Danfoss industrial cooling systems remain vulnerable and should not be directly reachable from the internet. | Official advisory, reported by Reuters |
What France’s investigation found
The French report says the compromises were concentrated in supermarkets but also reached smaller food businesses, including butchers, a slaughterhouse and co-operative food-processing plants. The same group targeted Schneider Electric equipment at several small hydroelectric sites at the same time, with more limited effects.
The official account is that defrost settings were changed, causing product losses and fires. Some news reports quote a setting of 50°C. A setpoint is what a controller was told to do, which is not the same as the temperature the product reached. That distinction matters later.
The UK angle
ITV reported on 3 November that some UK meat processors were affected in the second wave, reportedly because they used the same software as the affected European retailers. The Association of Independent Meat Suppliers said “a few” of its members were hit; fridges heated up overnight, but the units were empty and no meat was lost. The NCSC described the UK impact at that point as minimal. No major UK supermarket chain was reported as directly affected.
The UK was lucky with timing, not immune. As the meat processors showed, some of the same equipment is in use at UK sites.
What is not known
- How the attackers got in, in every case. Palo Alto Networks’ Unit 42 says the initial access vector “remains unconfirmed”. Reporting has pointed to outdated internet-connected equipment and default passwords, but no single route has been shown for every incident.
- Who was behind the November wave. France’s attribution covers October only. Pro-Russian hacktivist groups claimed responsibility for the November attacks on Telegram; Unit 42 describes those claims as unverified.
- How many devices were vulnerable. Unit 42 counted over 5,000 internet-visible devices from the affected manufacturers on 5 and 6 November. That measures exposure, not exploitable devices or victims. In France the count fell sharply after the alert, from 1,853 in the first half of October to 316 in the first week of November.
The evidence supports saying that attackers manipulated connected refrigeration control settings, and that internet-exposed control interfaces are a serious risk. It does not support blaming one brand, one protocol, one credential flaw or one remote access product for every incident.
Why a setting change becomes a physical incident
Operational technology (OT) is the equipment that monitors or acts on the physical world: PLCs, HMIs, drives, SCADA, refrigeration and building controllers. It is built to put safety, availability and timing first. The same access that lets an engineer inspect or adjust a machine lets anyone else do the same if the boundary fails.
The refrigeration attacks were integrity attacks. The aim was to change what the equipment did, not to steal information. The US fact sheet also warns of a denial-of-view condition, where operators can no longer see the real state of the process. The two can happen together: a setting is changed while the alarm or display that should reveal it is unavailable or misleading.
How it can unfold
| Stage | What can happen | The engineering question |
|---|---|---|
| Exposure | An internet-facing interface, unmanaged modem or supplier route allows contact with control equipment. | Which connections exist, and who owns them? |
| Access | Default or weak credentials, a known vulnerability or poor authorisation gives control. | Is every access authenticated, attributable and limited? |
| Change | Setpoints, timers, modes, recipes, logic or configuration are altered. | What can be changed remotely, and are limits enforced? |
| Physical effect | The process moves outside its normal operating range. | Do independent safeguards and alarms catch it? |
| Impact | Lost output, spoiled stock, downtime, a safety hazard. | Can the site contain it, find out what changed and recover? |
This is a risk model, not a reconstruction of the French incidents. A compromised interface does not necessarily mean a compromised PLC, and a changed PLC setting does not necessarily defeat an independent safety system. The outcome depends on process design, privileges, safeguards, network layout, monitoring and how people respond.
What it could mean in a factory
These are illustrative scenarios, not outcomes documented in the refrigeration cases:
- Food and drink. A changed cooking, chilling, cleaning or recipe parameter becomes a product quality or food safety question, and possibly a recall decision.
- Packaging. Changes to speed, sequencing or sensor logic create waste, jams or a stopped line.
- Process industries. Unauthorised changes to flow, pressure, dosing or temperature create equipment and safety hazards where protections are not independent.
After a suspected compromise, the questions go beyond “is the controller online?” Is the configuration the approved one? Can we trust the sensor readings? Is it safe to restart? Answering them needs automation engineers, operations, quality and security in the same room.
The controls that matter
These eight points come up again and again in the advice from CERT-FR, the US agencies, the NCSC and NIST. They are not a checklist for certification. How far you go with each depends on what a failure would cost on your site.
1. Know what is installed and how it can be reached
List every PLC, HMI, gateway, network switch and engineering laptop, with its firmware and software version. For each one, note which machine it runs, who owns it, how much a failure would hurt, whether the manufacturer still supports it, and which supplier looks after it.
Then list every way in. That means the 4G router the machine builder fitted in the panel, the remote support box on the network, any cloud service, and every supplier who can dial in. The NCSC treats these connections as part of the site’s architecture record. A list of PLCs that leaves out the machine builder’s router misses the kind of route these attacks rely on.
For each connection, note who starts it, what it carries, whether it can send commands, and who can switch it on or off. Gather this by looking and asking, not by scanning live equipment. Scanning or changing a running control system without a safe, agreed method can stop the line you are trying to protect.
2. Take control equipment off the open internet
CERT-FR’s first instruction was to take the affected controllers off the public internet. Where remote access was still needed, it should go back only through a VPN or protected network. Letting through only your contractors’ IP addresses buys time, but CERT-FR says it is not a fix. Germany’s BSI was blunter: industrial control systems “should not be directly accessible from the internet”.
The NCSC’s secure connectivity principles for OT, published in January 2026, point the same way: fewer ways in, all of them standard, all through one protected boundary. That does not mean every VPN is unsafe. What matters is how it is set up, who can use it, whether it is kept up to date and whether anyone watches it.
On a real site, that usually means replacing three or four suppliers’ own routes with one route you control. Each person who connects has their own login, with a second factor where the equipment allows it. They can reach only the machine they are supporting, the session is recorded and ends when the job does, and someone on site can switch it off. A connection nobody is using should not stay open just because it is convenient.
3. Separate the networks
Keep office IT, remote access, SCADA and the controllers that matter most on separate networks, and only allow the traffic each one needs. The US agencies’ minimum is a separate network for OT, away from office systems. IEC 62443-3-2 calls this zones and conduits. Separation limits how far an intruder can get once inside. It does not replace good passwords or safety engineering.
4. Change default passwords, keep firmware current, and plan for unsupported kit
Get rid of factory passwords, shared supplier logins and generic accounts. Keep a record of firmware and software versions, watch for manufacturer security notices, and install updates in planned maintenance windows after testing, with a way to roll back. The aim is not to patch everything mid-shift. Start with what is most exposed and would do most damage.
Equipment the manufacturer no longer supports needs the most care. CERT-FR warned that leaving unsupported devices on the internet carries a very high risk of compromise. It also warned that a factory reset is not enough on its own: it clears out the attacker but leaves the device open to the same attack the next day. If a device cannot be updated, put other protection around it and budget to replace it.
5. Protect the settings that matter
List the settings that would cause harm if someone changed them: oven and chiller temperatures, defrost timers, recipe limits, permissives, alarm limits, line speeds. Then find out who, and what, can change each one. The US agencies recommend setting sensible setpoint limits on downstream devices, with an alert when a setting moves outside them.
If the only alarm comes from the controller that has been tampered with, it cannot be fully trusted. Where the consequence justifies it, add a separate measurement, a separate alarm or a physical limit. Anything to do with machine safety should be designed and checked by competent safety engineers. Cyber security settings do not replace functional safety.
6. Record who changed what
You want to be able to say who connected, how, to which machine, when, with what rights, and what they changed or downloaded. Many older PLCs keep little or no log of their own, so the US agencies suggest recording the network traffic around them instead. Keep a copy of the approved program, configuration and settings, and compare against it.
A recording of a remote session is useful, but it does not prove every change was captured, that the logic is still safe, or that nobody came in another way. Check sessions against what changed in the controller, the approved change records and what the process itself is doing.
7. Be able to rebuild the machine, not just open the file
NIST’s OT Backup Quick Start Guide (SP 1339, June 2026) sets out what a restore needs. That means the program, logic and configuration files, firmware, HMI screens, licence keys, the manufacturer’s tools and the documentation. It also means the engineering software, the cable and a compatible spare to load it onto. NIST recommends protecting backups from being changed, keeping copies on site and off site, and regularly test-restoring them on equipment that is not in production.
A backup that has never been restored is an assumption. A restore also needs engineering checks before the machine runs again: interlocks, field settings, the current recipes, and a controlled restart. Measure how long a restore actually takes and what it depends on, not just how many backups you hold.
8. Plan how to cut off remote access, and practise it
Have a tested plan for disconnecting specific remote routes while the plant keeps running safely. Name who decides, which supplier to call, what safe running looks like, and how you reconnect afterwards. The NCSC warns that pulling a cable without understanding what depends on it can cause its own stoppage.
If you suspect an attack, make the process safe first, with site engineering and whoever is leading the response. Keep logs and configurations where it is safe to do so, and get specialist incident response help. Avoid unplanned resets, setting changes or scans: they can destroy the evidence or upset a running process.
A 90-day programme
This is an illustrative sequence, not a statutory deadline. Any work on production equipment should go through the site’s safety and change control procedures.
| Period | Priority | Evidence it is done |
|---|---|---|
| First 72 hours | Find any internet-exposed control interfaces and emergency supplier routes. Check current advisories. Review remote access and default passwords. Agree safe interim measures. | An approved exposure list, with an owner and action for each critical finding. |
| Days 4 to 30 | Complete the inventory of critical assets. Map supplier connections. Check setpoint limits and independent alarms. Test that access can be revoked. | Connectivity diagram, access review, recorded alarm and control tests. |
| Days 31 to 60 | Move to controlled, logged remote access and remove duplicate routes. Prioritise unsupported boundary devices. Establish a backup baseline. | Signed-off boundary design, access logs, a register of what each restore needs. |
| Days 61 to 90 | Exercise isolation and restoration. Assess remaining risk and supplier contracts. Approve a replacement programme for unsupported equipment. | Recovery exercise record, residual risk register, funded remediation plan. |
Deciding what to fix first
A label like “old PLC” or “connected machine” does not tell you where to start. Scoring each asset on four separate questions does:
- Exposure. Reachable from the internet, reachable through a governed boundary, or isolated?
- Privilege. What can someone with access do: view only, change setpoints, download programs, or affect safety functions?
- Consequence. Minor loss, extended downtime, or a quality or safety event?
- Recoverability. Tested recovery within target, uncertain, or no proven route?
An internet-reachable controller where setpoints can be changed, a change would affect food safety, and nobody has tested a restore goes to the top of the list. This is a practical triage built on the risk-based approach in NCSC, NIST and IEC 62443 guidance, not a published scoring standard.
Measuring progress
Useful measures include:
- the share of critical OT assets with a named owner and documented connections
- the number of unnecessary internet-facing management interfaces
- the share of supplier sessions with a named user, multi-factor authentication and expiry
- the share of critical setpoints with independently checked safeguards
- the number of unsupported devices reachable from outside
- the share of critical controller programs with a verified backup
- the share of recovery exercises completed within target.
A low number of reported incidents is not, on its own, evidence of good detection or control.
The regulatory picture in the UK
NIS2 does not apply to UK factories as UK law. It is EU legislation, though it can reach UK groups with EU sites and suppliers to in-scope EU businesses; our NIS2 guide for food groups covers how. In the UK, the NIS Regulations 2018 cover defined operators of essential services and digital service providers. The Cyber Security and Resilience Bill, which updates them and adds powers to designate critical suppliers, was still completing its passage through Parliament in November 2026. It is not a general requirement on every manufacturer that runs PLCs. Check scope against the law as enacted, sector regulator guidance and your contracts.
IEC 62443 is the international reference for industrial automation security, and IEC 62443-3-2 describes the zone and conduit risk assessment referred to above. “Aligned with IEC 62443 principles” is a different statement from independent certification of a product or a site; see IEC 62443 and your OT asset inventory.
Food manufacturers should also consider food safety and food defence controls, and customer certification requirements, where automated settings affect product safety. Our guide to BRCGS and PLC programs covers that ground. None of this guide is legal advice, a safety case or a certification opinion.
Ten questions for an engineering leadership review
Each answer should come with evidence, an owner and a review date, not an assurance that “IT handles security”.
- Can we list the controllers and gateways whose settings could materially change our process?
- Can we show every route by which a machine builder, contractor or remote service can reach them, including mobile data connections?
- Are any control interfaces reachable from the internet? If so, what is the justification and the compensating control?
- Who can change high-consequence parameters or programs, and how is each change approved and recorded?
- How would we detect an unauthorised change to a temperature, recipe, speed or other critical setting?
- Are our critical safeguards independent of the controller or monitoring path that might be compromised?
- Which gateways and controllers are unsupported, and when will they be replaced?
- Could we isolate supplier connections during a live incident, and when did we last test it?
- Have we proved we can restore critical programs and configurations onto suitable hardware?
- Who makes the joint production, safety and cyber decision to restart after a suspected compromise?
Where ECS fits, and where it does not
We are automation engineers, not a security operations centre. Some of the controls above are engineering work, and that is where we help.
| Need | What ECS provides | What it does not cover |
|---|---|---|
| Asset visibility | A Capture site audit records every PLC, HMI, drive and network device, with photos, firmware, lifecycle status and the backups we can take, without scanning your network. | Penetration testing or continuous network threat monitoring. |
| Configuration records | Command Centre holds the approved program versions, change history and device context for each asset. | It does not on its own guarantee that running logic is correct or that a process is safe. |
| Governed remote support | Connect sessions are authorised per visit and logged, with no always-on connection. | It does not remove other suppliers’ access routes or secure every boundary on site. |
| Recovery readiness | Programs, versions, software and cable details are recorded against each device, so a restore has what it needs. | Recovery still has to be tested on your equipment against your process requirements. |
| Remediation | Our automation projects team replaces unsupported controllers and rebuilds panels and networks. | Security architecture and assurance scope should be defined and, where the risk warrants it, independently reviewed. |
It would be wrong to claim that any one of these would have prevented the refrigeration attacks. What they do is give a site the visibility, control and recoverability that the rest of an OT security programme depends on. Where the risk justifies it, specialist OT security engineers and safety professionals should work alongside automation engineers.
The five questions that matter
The refrigeration attacks show that a cyber incident does not need ransomware or stolen data to stop a business. The answer is not to abandon connectivity: remote support is valuable and often necessary. It is to make every connection deliberate, governed, visible, isolatable and recoverable.
For each critical system, that comes down to five questions: what is installed, who can reach it, what can be changed, how would you know, and how would you get back to normal safely? A Capture audit answers the first two for every machine on site, and is usually the quickest place to start. If you would rather talk it through, contact us.
Sources
- CERT-FR, CERTFR-2026-ALE-012: Incident de sécurité ciblant les contrôleurs à distance des installations de réfrigération, 12 October 2026, updated 16 October 2026
- ANSSI and CERT-FR, CERTFR-2026-CTI-009, 9 November 2026, as reported by The Record
- CISA, FBI, HHS, USDA and US DOT, US Government Partners Urge Hardening Industrial Refrigeration and Cold Chain Monitoring Systems, 5 November 2026
- Palo Alto Networks Unit 42, Turning Up the Heat: Inside the Attacks on Europe’s Refrigeration Systems, 6 November 2026
- BleepingComputer, Hackers disrupt refrigeration systems at European supermarkets, 2 November 2026
- ITV News, UK meat processing firms hit amid fridge and freezer cyber attacks, 3 November 2026
- NCSC, Richard Horne’s speech at the NCSC Annual Review 2026 launch, 3 November 2026
- Reuters, German watchdog warns some cooling systems remain vulnerable to hacking, 13 November 2026, via The Star
- NCSC and partners, Secure connectivity principles for operational technology, January 2026
- NCSC and partners, Creating and maintaining a definitive view of your OT architecture
- NIST, SP 800-82 Rev. 3, Guide to Operational Technology (OT) Security, 2023
- NIST, SP 1339, OT Backup Quick Start Guide, June 2026
- IEC, IEC 62443-3-2: Security risk assessment for system design
- UK Parliament, Cyber Security and Resilience (Network and Information Systems) Bill
This guide summarises public information and published guidance. It is not a forensic analysis of the incidents, legal advice, or an assessment of any specific site.